Do Heat Pumps Work in Cold Weather? What the Data Says
Cold-climate heat pumps are rated at 47°F, 17°F and 5°F. Here is how efficient they are in the cold, how cold 21 US cities, the Midwest and Milwaukee actually get from NOAA normals, and what field tests found.
- Last reviewed Oct 26, 2026
- 19 cited sources
- 6 min read
- 1Yes: cold-climate heat pumps keep heating well below freezing, but efficiency falls as it gets colder. ENERGY STAR requires at least 70% of rated capacity and a COP of 1.75 at 5°F.
- 2In a DOE field test at 22 sites the median COP at 0–5°F was 1.9; one Minnesota unit measured about 1.3 at 10°F. Defrost and backup periods are left out.
- 3The coldest month’s average low is below 5°F in 4.4% of contiguous-US ZIP codes and 12.7% of Midwest ones (NOAA 1991–2020).
- 4Milwaukee’s airport averages 17°F in January with 6.6 nights a year at or below 0°F; inland suburbs run colder. Design temperatures: 2°F in Milwaukee County, −5°F in Waukesha County.
- 5Ask for capacity at your design temperature, not the nameplate; contractors size with ACCA Manual J.
Yes. A cold-climate air-source heat pump keeps heating well below freezing, but it gets less efficient as the air gets colder. To earn ENERGY STAR’s cold-climate label, a unit must still deliver at least 70% of its rated capacity at 5°F, at a coefficient of performance (COP) of 1.75 or better: 1.75 units of heat for every unit of electricity.5 In a Department of Energy field test at 22 sites, the median COP between 0°F and 5°F was 1.9.6 What changes in the cold is how much heat the unit can make, how often it defrosts, and when backup heat has to help.
Whether that matters depends on your winters. In NOAA’s 1991–2020 climate normals, the coldest month’s average low is below 17°F in 26.6% of ZIP codes in the contiguous US, and below 5°F in 4.4%.1 The Midwest runs colder; Milwaukee sits at its mild edge, with a 17°F January low at the airport and colder suburbs inland.
How efficient a heat pump is when it is cold
Electric resistance heat delivers a COP of 1; a heat pump does better because it moves heat instead of making it, and its COP falls as the outdoor air gets colder. Table 1 lines up what has been required and what has been measured.
| Source and equipment | Outdoor temperature | COP |
|---|---|---|
| Electric resistance backup heat | Any | 1.0 |
| Minnesota field study (CEE): one ducted unit, 2015–17, heat pump only | About 10°F | About 1.3 |
| Minnesota field study (CEE): same unit, heat pump only | 50–60°F | About 3.5 |
| DOE Challenge prototypes, 22 sites, 2022–24 (PNNL): median, defrost and backup excluded | 0–5°F | 1.9 |
| DOE Challenge prototypes (PNNL): median by temperature bin | Below 30°F | 1.6–2.7 |
| ENERGY STAR cold-climate and NEEP v4.0 minimum, at maximum capacity | 5°F | ≥ 1.75 |
| DOE Challenge requirement | 5°F | ≥ 2.4 up to 48,000 Btu/h, ≥ 2.1 above |
Read it as a range, not a promise. One of Minnesota’s ducted units delivered about 1.3 at 10°F in 2015–17;12 DOE’s prototypes, tested years later, a median of 1.9 at 0–5°F.6 Neither counts defrost minutes: a stretch of pure defrost has a COP near zero, because almost all the heat goes to the outdoor unit.12

What cold weather does to a heat pump
The colder the outdoor air, the harder it is to pull heat from it, so output and efficiency both fall. Pacific Northwest National Laboratory (PNNL) notes that a conventional heat pump’s capacity drops below its rating once it is colder than 40°F, and only a fraction is left in the teens.6 That is where the idea that heat pumps “don’t work in the cold” comes from. Cold-climate models close most of the gap with variable-capacity (inverter) compressors, which NEEP requires for its list.2 Ground-source (geothermal) systems are different: the ground 10 feet down stays at a constant temperature.10 Everything else here is about air-source units.
The three temperatures on a spec sheet: 47°F, 17°F and 5°F
NEEP’s list reports capacity and COP at 47°F, 17°F and 5°F, plus the lowest temperature the manufacturer publishes data for.2 47°F is a mild day, 17°F a normal January night in Chicago (19°F) or Albany (16°F), and 5°F deep cold. ENERGY STAR tests cold-climate units down to 5°F and notes that they keep running below it.4
What makes a heat pump “cold-climate”
NEEP’s specification is a minimum for efficiency-program qualification, and NYS Clean Heat requires it for rebates.10 DOE’s Cold Climate Heat Pump Challenge set a stricter target that eight manufacturers built prototypes for.8
| Requirement | ENERGY STAR | NEEP ccASHP v4.0 | DOE Challenge |
|---|---|---|---|
| COP at 5°F (max capacity) | ≥ 1.75 | ≥ 1.75 | ≥ 2.4 (24,000–48,000 Btu/h), ≥ 2.1 above |
| Capacity at 5°F vs. 47°F | ≥ 70% | Must be reported (47, 17, 5°F) | 100% |
| HSPF2 (seasonal efficiency) | ≥ 8.1 ducted, ≥ 8.5 ductless | ≥ 7.7 ducted, ≥ 8.5 non-ducted | Not listed here |
| Compressor | Not listed here | Variable capacity | Cut-out no higher than −10°F |
Sources: PNNL’s summary of the ENERGY STAR criteria,5 NEEP2 and DOE;7 see what HSPF2 measures. PNNL says a properly sized heat pump
can meet 100% of a home’s heating load in nearly any location
To check a model, look it up on NEEP’s cold-climate heat pump product list3 or ask whether it is ENERGY STAR cold-climate certified.
How cold it gets where you live
A 5°F rating matters only if your winters get near 5°F. We found the coldest month for every contiguous-US ZIP code in NOAA’s 1991–2020 normals, using the nearest weather station.1 Of 40,565 ZIP codes, 26.6% average below 17°F in that month and 4.4% below 5°F, mostly in Minnesota, the Dakotas and Wisconsin, with pockets in northern New England and the Rockies. Nights below zero are more widespread: half of all ZIP codes average at least one a year, and 18.7% average ten or more.

For 21 cities, the coldest month sits next to the design temperature that load calculations use: ENERGY STAR’s Design Temperature Limit Reference Guide gives each county a 99% heating design temperature from ASHRAE and ACCA Manual J data.9

| City (ZIP) | Coldest month | Average low | Nights ≤10°F | Nights ≤0°F | 99% design temp. |
|---|---|---|---|---|---|
| Fargo, ND (58102) | Jan | 0°F | 71 | 42 | −15°F |
| Minneapolis, MN (55401) | Jan | 8°F | 46 | 23 | −8°F |
| Madison, WI (53703) | Jan | 11°F | 42 | 20 | −3°F |
| Burlington, VT (05401) | Jan | 13°F | 38 | 16 | −4°F |
| Des Moines, IA (50309) | Jan | 14°F | 28 | 10 | −2°F |
| Omaha, NE (68102) | Jan | 15°F | 27 | 9 | −2°F |
| Portland, ME (04101) | Jan | 16°F | 27 | 7 | 2°F |
| Albany, NY (12207) | Jan | 16°F | 24 | 7 | 1°F |
| Chicago, IL (60602) | Jan | 19°F | 16 | 4 | 2°F |
| Detroit, MI (48226) | Jan | 20°F | 12 | 2 | 6°F |
| Pittsburgh, PA (15222) | Jan | 20°F | 11 | 2 | 9°F |
| Denver, CO (80202) | Dec | 21°F | 16 | 4 | 3°F |
| Columbus, OH (43215) | Jan | 21°F | 13 | 4 | 9°F |
| Kansas City, MO (64106) | Jan | 22°F | 10 | 1 | 9°F |
| Boston, MA (02108) | Jan | 23°F | 7 | 1 | 12°F |
| Spokane, WA (99201) | Dec | 24°F | 9 | 2 | 9°F |
| Nashville, TN (37201) | Jan | 28°F | 3 | <1 | 18°F |
| Salt Lake City, UT (84101) | Jan | 28°F | 1 | <1 | 14°F |
| New York, NY (10001) | Jan | 28°F | 3 | <1 | 13°F |
| Atlanta, GA (30303) | Jan | 34°F | <1 | <1 | 25°F |
| Seattle, WA (98101) | Dec | 36°F | <1 | <1 | 27°F |
Nights at or below 0°F and 10°F are NOAA’s average days a year with a low at or below that mark, at the same station. For a county with several stations, ENERGY STAR uses the coldest.9
What monthly normals can and can’t tell you
- An average hides cold nights. Minneapolis averages an 8°F January low, yet 23 nights a year below zero.
- Design temperatures are colder. In every city in Table 3, the 99% design temperature is 8.5 to 17.6°F below the coldest month’s average low. Equipment selection starts from the design temperature.9
The nearest station can be miles away and valleys run colder than hilltops; our methodology page explains the matching. We also re-pulled the 29 stations in Tables 3 and 5 from NCEI’s public data service: every figure matched.
Manufacturer low-temperature claims against real design nights
Trane says its low-profile cold-climate models “can provide 100% of your heat down to 5 degrees Fahrenheit,” and that its newest model provides 105% of heating needs down to 5°F and 84% down to −20°F.13 Carrier says its 27VNA1 keeps “reliable performance without a loss of heating power” down to −23°F.14 Those are the manufacturers’ own statements; we could not test them. For scale, in Table 3 11 of 21 cities have a design temperature at or above 5°F, and the coldest, Fargo, is −15°F, warmer than either claim.
The Midwest and Milwaukee: how cold, and what it means
Table 4 groups the 12 states of the Census Bureau’s Midwest region,15 11,378 ZIP codes, by NOAA’s coldest-month average low and by nights at or below 0°F.1 The region’s median ZIP code has a coldest-month low of 16°F, against 23°F for the contiguous US, and 12.7% of its ZIP codes average below 5°F, about three times the national share. The spread is wide: 94% of North Dakota and about two-thirds of Minnesota ZIP codes are below 5°F; no ZIP code in Illinois, Indiana, Ohio, Kansas, Missouri or Nebraska is.

| State | ZIPs | Median low | Under 17°F | Under 5°F | 10+ nights ≤0°F |
|---|---|---|---|---|---|
| North Dakota | 407 | −0.4°F | 100.0% | 94.1% | 100.0% |
| Minnesota | 992 | 3.4°F | 100.0% | 67.5% | 100.0% |
| South Dakota | 385 | 7.1°F | 99.2% | 33.5% | 100.0% |
| Wisconsin | 896 | 8.7°F | 98.7% | 25.0% | 92.7% |
| Iowa | 1,055 | 10.3°F | 100.0% | 1.3% | 96.1% |
| Nebraska | 620 | 13.6°F | 99.0% | 0.0% | 67.6% |
| Michigan | 1,159 | 15.9°F | 63.5% | 2.5% | 31.9% |
| Illinois | 1,575 | 17.7°F | 42.0% | 0.0% | 22.6% |
| Indiana | 968 | 18.8°F | 19.5% | 0.0% | 1.3% |
| Kansas | 748 | 19.1°F | 21.7% | 0.0% | 0.0% |
| Ohio | 1,416 | 20.1°F | 9.2% | 0.0% | 0.0% |
| Missouri | 1,157 | 21.7°F | 12.4% | 0.0% | 3.4% |
| Midwest, 12 states | 11,378 | 16.0°F | 55.9% | 12.7% | 42.4% |
| Contiguous US | 40,565 | 23.1°F | 26.6% | 4.4% | 18.7% |
Shares count ZIP codes, not people.
Greater Milwaukee: mild at the airport, colder inland
Wisconsin’s median ZIP code averages 8.7°F in its coldest month; Milwaukee is at the mild end. NOAA’s normals for Mitchell International Airport give a January average low of 17.2°F and 6.6 nights a year at or below 0°F, about the subzero count of Albany or Portland, Maine in Table 3. Inland it changes: Waukesha averages 12°F in January with about 15 such nights, and Hartford 8.5°F with about 22, close to Minneapolis.1
| Place (ZIP) | Jan. avg. low | Nights ≤10°F | Nights ≤0°F | County design |
|---|---|---|---|---|
| Milwaukee, airport area (53221) | 17.2°F | 22 | 6.6 | 2°F |
| Kenosha, airport (53144) | 16.4°F | 27 | 10.1 | 3°F |
| Racine, airport (53402) | 16.0°F | 24 | 7.7 | −2°F |
| Milwaukee, downtown (53202) | 14.7°F | 29 | 8.1 | 2°F |
| Brookfield (53005) | 14.1°F | 28 | 10.5 | −5°F |
| Waukesha (53186) | 12.2°F | 37 | 14.8 | −5°F |
| West Bend (53095) | 10.7°F | 38 | 16.2 | 1°F |
| Hartford (53027) | 8.5°F | 43 | 21.6 | 1°F |

ENERGY STAR gives one design temperature per county, from one station,9 so it cannot show the gradient inside a county: Washington County’s 1°F is warmer than Waukesha County’s −5°F, yet Hartford, in Washington County, has colder Januarys than Waukesha. Ask which design temperature your Manual J calculation uses.
What that means for a heat pump in Milwaukee
- The design night is near the 5°F test point. Milwaukee County’s 99% design temperature is 2°F, 3°F colder than the point where ENERGY STAR checks capacity. In Waukesha County it is −5°F, 10°F below it.
- Minnesota’s study is the nearest field evidence. The Center for Energy and Environment (CEE) monitored six Minnesota homes through two winters, with backup heat taking over at about 10°F. It estimated that this lets the heat pump supply 81% of the heating load in Minneapolis and 71% in Duluth.12 Milwaukee is milder, so its share would likely be higher, but how much needs hourly temperatures, which normals do not contain.
- Minnesota’s savings figures do not answer the furnace question. CEE estimated 36% to 56% less site energy than propane furnaces or electric baseboards, not natural gas.12 Whether a heat pump costs less than gas in Milwaukee depends on local prices; our heat pump vs. furnace guide shows the break-even method, with Madison and Chicago as the nearest cities in its table.
- Check the weather basis of any quote. One southeastern Wisconsin installer’s comparison, from On Time Heating & Cooling, uses a 5°F design day and about 7,300 heating degree days.16 NOAA’s normals give 6,450 at Mitchell Airport and 7,420 at West Bend; ENERGY STAR lists 2°F for Milwaukee County. Stations and years differ; see how heating degree days work.
How cold-climate units did in real homes
From 2022 to 2024, PNNL monitored DOE Challenge prototypes at 22 sites in the northern US and Canada: occupied single-family homes, apart from Canadian test facilities. All were ducted, most were 3-ton units, and all had staged electric backup.6 Leaving out defrost and backup periods, median COPs below 30°F ran from 1.6 to 2.7, and most units beat the 1.75 minimum at 5°F. In Minnesota, CEE’s field study found that its cold-climate units
performed to their rated specifications for both system capacity and efficiency
That fits PNNL’s later results, with three limits. PNNL’s units were pre-commercial prototypes, and its sites came from lists each manufacturer supplied, with homeowners who were employees or affiliates of the manufacturers.6 Many sites had milder winters than normal: backup elements ran about 25% of the time between −10°F and 0°F, but that rests on 8 and 11 of the 22 sites. And CEE’s equipment dates from 2015–17. New York’s energy agency (NYSERDA) likewise found that properly sized cold-climate units gave adequate heat and comfort.10 Read the PNNL field report (PNNL-37127).
Defrost cycles: why the outdoor unit ices up
In cold, humid weather, moisture freezes on the outdoor coil, and the frost cuts how much heat the unit can pull from the air. To clear it, the heat pump briefly reverses into cooling mode, moving heat to the outdoor coil to melt the frost.6 The air from your vents can turn cooler meanwhile; PNNL found most units kept the fan running with the first stage of backup heat, about 5 kW. That is normal, though defrost can use significant energy. In CEE’s study the controls started defrost whenever frost was possible, which the report says uses more energy than waiting until frost forms.12
Balance point and backup heat
As it gets colder, your home needs more heat while the heat pump makes less. Where those lines cross is the balance point; below it, PNNL explains, the heat pump cannot meet the home’s needs without backup.5

Where it lands is a design choice. In PNNL’s Minneapolis example, four sizing approaches put it at 40°F, 30°F, 0°F or −15°F.5 CEE’s Minnesota home shows the same effect with real equipment: against a load of 38,000 Btu/h at −11°F, the crossover was 5°F for a 4-ton unit, 14°F for a 3-ton and 27°F for a 2-ton.12
Backup is electric resistance strips or a furnace (dual fuel). ENERGY STAR notes that a cold-climate unit keeps working below 5°F, but that a backup source heats most efficiently when it is even colder.4 Resistance heat has a COP of 1, so hours on backup cost more than heat pump heat; whether gas backup is cheaper is a rates question, covered in our running-cost guide.

The switchover temperature, below which backup may run, is programmed into the thermostat. In the field it varied from home to home, which PNNL attributes most likely to thermostat programming and occupant behavior calling for backup in warmer weather. It also saw thermostat setbacks trigger backup heat, and suggests holding one temperature or making setbacks gradual.6 If bills spike on mild days, ask the installer to check the setting.
How to get good performance in a cold winter
- Choose a cold-climate model: ENERGY STAR cold-climate certified or on NEEP’s list.
- Ask for capacity at your design temperature. PNNL says equipment should not be selected on nameplate capacity.5
- Seal and insulate first. NYS Clean Heat recommends an energy assessment and air sealing before sizing.10
- Keep the outdoor unit above the snow. NYS Clean Heat advises mounting it at least 18 inches above the ground, on a gabled side of the house.10
- Ask how backup is set up: its type, stages and switchover temperature.
- Plan for outages. A heat pump stops when the power does; our generator size calculator sizes a backup unit for your elevation.
NEEP’s specification puts the second point plainly: consumers, contractors and designers should
review building loads, equipment capacities at design temperatures, and other important factors

Related guideHow to Winterize Your House: A Fall Checklist With DatesNext step
Compare your city’s design temperature in Table 3 or Table 5 with the 5°F figure on any quote, then check running costs in our heat pump vs. furnace guide. More: heating and cooling guides, home energy, climate guides.
Frequently asked questions
Efficiency (COP) falls as the air gets colder. ENERGY STAR and NEEP require at least 1.75 at 5°F. In PNNL’s field test of 22 DOE Challenge prototypes the median was 1.9 at 0–5°F and 1.6 to 2.7 below 30°F, with defrost and backup periods left out; one Minnesota unit measured about 1.3 at 10°F. Electric resistance heat is 1.0.
There is no single cutoff. Conventional heat pumps lose capacity below 40°F and keep only a fraction in the teens, PNNL says. Cold-climate models are tested at 5°F and keep running below it; DOE’s Challenge prototypes had to run down to at least −10°F, and NYS Clean Heat cites research showing comfortable heating at −15°F.
Yes, with a cold-climate model sized for the home. Milwaukee’s airport averages 17°F in January and ENERGY STAR lists 2°F as the county design temperature, near the 5°F test point. Inland suburbs, Minnesota and the Dakotas are colder, so ask for capacity at your design temperature.
Usually some. All 22 sites in PNNL’s field test had electric backup. How often it runs depends on sizing against your design temperature, which a contractor works out with ACCA Manual J.
Most often it is a defrost cycle. The unit briefly reverses to melt frost off the outdoor coil, which can cool the air at the vents; many systems run a stage of backup heat to make up for it. Ice that does not clear is a job for a licensed contractor.
Output and efficiency fall as it gets colder, so backup heat may have to help on the coldest nights, and electric resistance backup (COP 1) costs more to run.
Keep the outdoor unit above the snow (NYS Clean Heat advises at least 18 inches), seal air leaks, and have the installer check the backup switchover setting. PNNL saw thermostat setbacks trigger backup heat and suggests holding one temperature or making setbacks gradual.
Long run times are normal for variable-speed units. In PNNL’s field test, median heating cycles between 5°F and 30°F lasted 50 to 200 minutes, and some sites ran close to 25 hours without stopping.
It depends on local electricity and gas prices, not only on the cold; our heat pump vs. furnace guide shows the break-even method. Minnesota’s CEE study estimated savings against propane furnaces and electric baseboard heat, not natural gas.
Sources
Sources labeled Compared are popular pages we checked our answer against. They are not extension, government, standards or manufacturer sources. How we choose sources
- 1.U.S. Climate Normals 1991–2020 (monthly and annual/seasonal station normals; re-pulled from the NCEI data service). NOAA National Centers for Environmental Information, 2021. Used for: coldest-month average lows for every ZIP and city; average nights a year below 0°F and 10°F; Midwest and Milwaukee tables Back to text
- 2.Cold Climate Air Source Heat Pump Specification, Version 4.0. Northeast Energy Efficiency Partnerships (NEEP), 2023. Used for: variable-capacity compressor, HSPF2 and COP at 5°F minimums, 47/17/5°F reporting, design-temperature quote Back to text
- 3.ccASHP Specification & Product List. Northeast Energy Efficiency Partnerships (NEEP), accessed 2026. Used for: product list; specification purpose and climate zones Back to text
- 4.Air-Source Heat Pumps. ENERGY STAR (U.S. EPA), accessed 2026. Used for: cold-climate units tested to 5°F, running below it, and backup heat pairing Back to text
- 5.Cold Climate Heat Pump Sizing and Selection. Pacific Northwest National Laboratory, Building America Solution Center, accessed 2026. Used for: ENERGY STAR cold-climate criteria, balance point, Minneapolis sizing approaches, nameplate capacity, Manual J/S Back to text
- 6.Performance Results from DOE Cold Climate Heat Pump Challenge Field Validation (PNNL-37127). Pacific Northwest National Laboratory (Mendon et al.), 2025. Used for: field COPs, backup heat use, defrost, switchover, thermostat setbacks, run times, satisfaction, site selection Back to text
- 7.Residential Cold-Climate Heat Pump Technology Challenge Specification, Version 1.2. U.S. Department of Energy, 2021. Used for: 100% capacity and COP 2.1–2.4 at 5°F; compressor cut-out Back to text
- 8.Residential Cold Climate Heat Pump Challenge. U.S. Department of Energy, accessed 2026. Used for: eight participating manufacturers Back to text
- 9.ENERGY STAR Certified Homes Design Temperature Limit Reference Guide (rev. 09/01/2018). ENERGY STAR (U.S. EPA), 2018. Used for: 99% heating design temperature by county Back to text
- 10.Do Heat Pumps Really Work in Cold Climates? NYS Clean Heat (NYSERDA and New York utilities), accessed 2026. Used for: inverter compressors and defrost controls, ground-source heat pumps, NEEP requirement, NYSERDA finding, air sealing, 18-inch mounting Back to text
- 11.Manual J: Residential Load Calculation. Air Conditioning Contractors of America (ACCA), accessed 2026. Used for: load calculation standard
- 12.Cold Climate Air Source Heat Pump (CARD field assessment report). Center for Energy and Environment for the Minnesota Department of Commerce, 2017. Used for: six Minnesota homes: COP at 10°F, defrost, sizing and changeover temperature, share of load, savings baselines, conclusion on rated performance Back to text
- 13.Cold Climate Heat Pumps (CCHPs). Trane Technologies, accessed 2026. Used for: manufacturer statements on capacity at 5°F and −20°F Back to text
- 14.Cold Climate Heat Pump Systems. Carrier, accessed 2026. Used for: manufacturer statement on performance down to −23°F Back to text
- 15.Census Regions and Divisions of the United States. U.S. Census Bureau, n.d. Used for: the 12 Midwest states used in Table 4 Back to text
- 16.Compared Furnace vs Heat Pump in a Wisconsin Home. On Time Heating & Cooling, 2026. Used for: installer’s stated design day and heating degree days for southeastern Wisconsin Back to text
- 17.Ice on the heat pump closeup (photo). Shixart1985, Wikimedia Commons, CC BY 2.0, 2023. Used for: photo, cropped
- 18.Destroyed heat pump (photo). Ignatus, Wikimedia Commons, CC0, 2012. Used for: photo, cropped
- 19.Display controller for LG heat thermal pump indoors (photo). Nenad Stojkovic, Wikimedia Commons, CC BY 2.0, 2021. Used for: photo, resized
How this guide was made
- Written by the Home Systems Desk and reviewed by the Data & Methodology Desk.
- Data: coldest-month average lows from NOAA NCEI U.S. Climate Normals 1991–2020 for the station nearest each ZIP code, and average nights a year below 0°F and 10°F from the same release and station (the 29 stations used in Tables 3 and 5 were re-pulled from NCEI’s data service on 2026-10-26 and matched); Midwest shares count ZIP codes in the 12 Census Bureau Midwest states, not people; Greater Milwaukee rows use these stations: Milwaukee Mitchell International Airport (53221), Kenosha Regional Airport (53144), Racine Batten Airport (53402), West Allis (downtown 53202), Mount Mary College (Brookfield 53005), Brookfield wastewater plant (Waukesha 53186), West Bend Public Works (53095) and Hartford wastewater plant (53027); 99% heating design temperatures from the ENERGY STAR Design Temperature Limit Reference Guide (2018), one value per county; specifications from NEEP v4.0, ENERGY STAR (as summarized by PNNL) and DOE’s Challenge specification; field results from PNNL report PNNL-37127 (2025) and the Center for Energy and Environment’s Minnesota report (2017); manufacturer figures are the manufacturers’ own statements. The balance-point chart is an illustration, not a sizing calculation. See our methodology.
- AI use: AI tools help us research, draft and check this guide. Every figure is checked against the source cited for it, and calculated figures come from our own code, described on the methodology page.
- Spotted an error? Tell us and the form opens with this page’s address filled in.
Change log
- Oct 26, 2026Review and expansion: re-read the NEEP, PNNL, PNNL-37127, ENERGY STAR, NYS Clean Heat, DOE, Trane and Carrier pages against the quotes and figures here. Added a COP-by-temperature table, a Midwest state table and a Greater Milwaukee section with NOAA lows, subzero-night counts and county design temperatures, Minnesota field-study findings (Center for Energy and Environment), a note on manufacturer low-temperature claims, and field-study limits (prototypes, manufacturer-affiliated homeowners, mild winters). Corrections: the share of ZIP codes below 17°F is 26.6% (it said about 26%, a rounding of two rounded parts); the field test had 22 sites, not 22 occupied homes (some were Canadian test facilities). Search title changed to match efficiency queries; the FAQ now has 9 questions (the “20-degree rule” question was dropped because it no longer appears in related searches). No other figure changed.
- Oct 22, 2026Review: re-read the NEEP, PNNL, PNNL-37127, ENERGY STAR and NYS Clean Heat pages against the quotes and figures here; merged the two temperature questions in the FAQ, added the 20-degree rule question (no source uses that name), shortened a table header so Table 1 fits a phone screen.
- Oct 6, 2026Clarified that NOAA night counts are nights at or below 0°F and 10°F
- Oct 4, 2026Review: re-checked the PNNL, PNNL-37127 and NEEP quotes and the ENERGY STAR, NEEP, PNNL and NYS Clean Heat figures against the live sources; added a note that ground-source (geothermal) heat pumps are not affected by air temperature (NYS Clean Heat).
- Oct 2, 2026Published. Coldest-month lows and nights below 0°F/10°F for every contiguous-US ZIP from NOAA 1991–2020 normals, compared with ENERGY STAR 99% design temperatures for 21 cities; specifications checked against NEEP v4.0, ENERGY STAR (via PNNL) and DOE; field results from PNNL-37127.
Covers heating, cooling, generators and water heaters. We maintain the generator sizing calculator and write the guides that explain what a number means before you call a contractor.
Keep reading
What Size Generator to Run a Furnace? Watts for Gas, Oil and Electric Heat
A gas or propane furnace needs about 300–875 running and 1,600–2,350 starting watts. What oil furnaces, electric furnaces and heat pumps draw, from generator charts and furnace spec sheets, with the altitude derate for 15 cold-winter cities.
What Temperature Should a Water Heater Be Set At? 120°F, and When to Go Higher
Most homes should run a water heater at 120°F. What DOE, CDC, CPSC, EPA and OSHA each say, how fast hotter water burns, and what a lower setting really saves.
Portable Generator Safety: The Rules and the CPSC Data Behind Them
Outdoors only, 20 feet from the house, exhaust away, CO alarms on every level. CPSC records of 789 generator CO deaths show why each rule exists.
Seasonal reminders for your ZIP
Get a short email when it’s time to overseed, start seeds, open the pool or service your furnace, timed to your climate.




