Home Energy Guide

What Size Generator to Run a Furnace? Watts for Gas, Oil and Electric Heat

What gas, propane, oil and electric furnaces and heat pumps really draw, from generator makers’ charts and furnace spec sheets, with the altitude derate for 15 cold-winter cities.

HS
Published Oct 5, 2026
Bar chart of generator running and starting watts for gas, oil and electric furnaces and heat pumps
Eaves & Acres chart: what each heating system asks of a generator, from Champion, Honda, Beckett and Goodman figures.Chart: Eaves & Acres
Key takeaways
Checked Nov 23, 2026
  1. 1A gas or propane furnace’s blower needs about 300–875 running and 1,600–2,350 starting watts (Champion, Honda); with a fridge, lights and TV, a 3,000 W generator covers it at sea level.
  2. 2Nameplate amps × volts is a ceiling, not the draw: Thermo Pride’s ECM blower uses 215–309 W in heating against 512–682 W for its PSC model.
  3. 3Electric furnaces and heat pumps run on 240 volts; a 9.6 kW electric furnace needs a 12 kW generator.
  4. 4Altitude costs about 3.5% per 1,000 ft (Honda). In the coldest 31% of ZIP codes, 1 in 7 lose 10%+; Flagstaff needs 3,662 starting watts for the same furnace load.
  5. 5Lennox asks for generator power under 5% THD. A licensed electrician installs the transfer switch, and the generator runs outside, 20+ feet away (CPSC).

A gas or propane furnace needs only enough generator power for its blower, inducer fan, igniter and controls: about 300 to 875 running watts, plus a short surge to 1,600–2,350 watts as the blower starts, according to Champion’s and Honda’s wattage charts.1,2 The furnace alone fits a 2,000-watt generator whose starting rating covers that surge, and a 3,000-watt unit runs it with a fridge, lights and a TV at sea level. An oil furnace adds its burner. An electric furnace or a heat pump is a different class of load: about 4,300 to 25,000 running watts, on 240 volts.

Below, we check those chart numbers against furnace makers’ own blower data and add our NOAA altitude analysis: in the coldest third of US ZIP codes, about 1 in 7 lose 10% or more of a portable generator’s output.

Sizing estimate, not electrical advice. This page estimates watts and gives no wiring instructions. Connecting a furnace to a generator takes a transfer switch installed by a licensed electrician. Follow your furnace’s and generator’s manuals. This is educational information, not professional advice; see our disclaimer.

How many watts each type of furnace draws

The fuel makes the heat. Electricity runs what moves the air and lights the burner. In a gas furnace, that means the circulating blower, the inducer fan that pulls combustion gases through, a hot-surface igniter and the control board.8,9 Propane furnaces are the same machines: Carrier approves its 58SC models for natural gas or propane, converted with a gas kit.8

Table 1. What each heating system asks of a generator (sea level)
Heating systemWhat runs
on electricity
Running
watts
Starting
watts
Volts
Gas or propane
furnace
Blower, inducer fan, igniter, controls300–800 (Champion, 1/2 hp fan); 875 (Honda, 1/2 hp)800–1,600 (Champion); 2,350 (Honda)115–120
Oil furnaceBlower, plus the oil burner’s motor, igniter and controlBlower + up to about 700 for the burner (5.8 A maximum)The blower’s surge120
Heat pump, 3-tonCompressor and outdoor fan, indoor blower3,000–3,500 for the compressor, plus the blower5,000–6,000208–240
Electric furnace
or heat strips
Resistance elements, blower3,000–24,000 for the elements, plus the blowerNo surge from the elements208–240

For a gas furnace the blower is nearly the whole load; an oil burner adds up to 5.8 amps.11 Honda’s wattage estimation guide lists furnace fans for gas or fuel oil by size, from 300 running and 500 starting watts for a 1/8 hp fan up to 875 and 2,350 for a 1/2 hp fan.2 Champion’s wattage chart gives a 1/2 hp furnace fan 300–800 running and 800–1,600 starting watts.1 Our generator size calculator uses Champion’s top figures. If you don’t know your blower’s size, Honda’s 2,350 is the safer starting number.

Even Honda’s own pages differ: one lists a 1/4 hp furnace fan at 1,600 starting watts, another at 1,000.2,3 Plan on the top of a range.

How to read your own furnace’s numbers

Spec sheets and rating labels give volts and amps. Multiplied, they give a ceiling, not the running draw. Carrier’s 58SC gas furnaces list maximum unit amps of 5.6 to 13.4 at 115 volts, depending on size: about 640 to 1,540 watts.8 Thermo Pride’s OL6 oil furnace lists a total current of 8.7 amps with its 1/2 hp PSC blower, about 1,040 watts at 120 volts. Its own blower table shows 512 to 682 watts at the heating speeds.10

Skip the “minimum circuit ampacity” line. Goodman defines it as 1.25 times the blower amps plus the inducer amps, a wire-sizing figure.9 And none of the Carrier, Goodman, Lennox or Thermo Pride documents we read gives a starting figure for the blower, so the generator makers’ charts are the only published surge numbers.

Older PSC blowers and newer ECM blowers

What a blower really draws depends on its motor. Thermo Pride publishes watts for two versions of its OL6 oil furnace. At 0.5 inch of static pressure, the 1/2 hp PSC (permanent split capacitor) blower draws 512 to 682 watts at the heating speeds, and the 1 hp ECM version draws 215 to 309 watts.10 On the top (cooling) speed the two are close: 869 and 855 watts.

Bar chart of oil furnace blower watts in heating: PSC motor 512 to 682 W, ECM motor 215 to 309 W
Eaves & Acres chart from Thermo Pride’s OL6 spec sheet: the ECM blower draws less than half as much at the heating speeds.

Federal rules push the same way. Furnace fans made on or after July 3, 2019 must meet DOE’s fan energy rating limits.14 For the 3-ton gas furnace in DOE’s 2012 analysis, which moves 1,158 cubic feet of air a minute, the limit works out to about 233 watts per 1,000 cfm, against 380 for the old PSC baseline. DOE put that baseline blower at 382 watts in heating.14,15

A furnace made since 2019 may run well under the chart figures, but no document we read says how much less it needs to start, so keep the chart’s starting watts.

Worked examples: gas, propane and oil furnaces

Each example uses our calculator’s rule: running watts plus 5%, divided by the altitude factor (Honda: about 3.5% less power per 1,000 feet),4 and a starting rating of at least the starting total divided by the same factor. Elevations are for the NOAA station nearest each city.17

Worked example

Gas or propane furnace in a Chicago outage

Scenario
Furnace (800 running, 1,600 starting), fridge (400, 1,200), lights (300) and a TV with router (420). NOAA station elevation 583 ft.
Math
Running: 800 + 400 + 300 + 420 = 1,920 W. Largest surge: the furnace or the fridge, 800 W each. Starting: 2,720 W. Altitude factor: 1 − 0.035 × 0.583 = 0.980. Size: 1,920 × 1.05 ÷ 0.980 = 2,058 W. Starting: 2,720 ÷ 0.980 = 2,777 W.
Answer
A 3,000-watt generator rated for at least 2,777 starting watts.
Worked example

Oil furnace in Boston

Scenario
1/2 hp blower (Honda: 875 running, 2,350 starting), oil burner (up to 5.8 A × 120 V = 696 W), fridge, lights and a TV with router. Station elevation 12 ft.
Math
Running: 875 + 696 + 400 + 300 + 420 = 2,691 W. Largest surge: the blower, 2,350 − 875 = 1,475 W. Starting: 4,166 W. Altitude barely matters (factor 0.9996). Size: 2,691 × 1.05 ÷ 0.9996 = 2,827 W. Starting: 4,166 ÷ 0.9996 = 4,168 W.
Answer
A 3,000-watt generator rated for at least 4,168 starting watts.
Worked example

The same gas furnace in Flagstaff

Scenario
The Chicago list in Flagstaff, Arizona. Station elevation 7,347 ft.
Math
Altitude factor: 1 − 0.035 × 7.347 = 0.743. Size: 1,920 × 1.05 ÷ 0.743 = 2,714 W. Starting: 2,720 ÷ 0.743 = 3,662 W.
Answer
Still a 3,000-watt generator, but one rated for at least 3,662 starting watts, about a third more than in Chicago.

Staggering loads shrinks these numbers. Honda’s guide puts it plainly:3

it is not necessary to power everything at the same time.

In Honda’s example, a 3,000-watt generator runs a fridge, furnace, lights, TV and microwave easily, and as little as 1,600 watts can do if the furnace and fridge run at separate times and the lights and TV go off whenever one of them starts.3

Altitude: cold places lose more generator power

Engines make less power in thin air, and many places that lean hardest on a furnace are high. We applied Honda’s 3.5%-per-1,000-ft rule to the NOAA station nearest each of 40,789 ZIP codes with both an elevation and a heating degree day normal.4,17 Nationally, 8.6% lose 10% or more of a portable’s power. In the coldest 31% (6,000 heating degree days or more), 13.6% do, about 1 in 7; in the mildest band, under 2,000 degree days, 0.6%. About half of all the ZIP codes losing 10% or more are in that cold group.

Bar chart of US ZIP codes losing 10% or more generator power to altitude, rising from 0.6% to 14.9% in colder climates
Eaves & Acres analysis of NOAA normals: the colder the climate, the more often altitude cuts a portable generator’s output.
Table 2. Generator for a gas furnace in 15 cold-winter cities: size (starting rating), NOAA 1991–2020 normals, nearest station
CityStation
elevation
Heating
degree days
Power
lost
Furnace, fridge,
lights, TV
Plus sump pump,
microwave
Boston, MA12 ft5,545under 0.1%3,000 W (2,721)5,000 W (4,722)
Chicago, IL583 ft6,0182.0%3,000 W (2,777)5,000 W (4,818)
Detroit, MI626 ft6,1062.2%3,000 W (2,781)5,000 W (4,826)
Buffalo, NY693 ft6,4662.4%3,000 W (2,788)5,000 W (4,837)
Pittsburgh, PA717 ft5,3792.5%3,000 W (2,790)5,000 W (4,841)
Minneapolis, MN754 ft7,6992.6%3,000 W (2,794)5,000 W (4,848)
Spokane, WA2,353 ft6,4638.2%3,000 W (2,964)5,000 W (5,144)
Billings, MT3,097 ft6,95510.8%3,000 W (3,051)5,000 W (5,294)
Boise, ID3,885 ft6,16713.6%3,000 W (3,148)5,000 W (5,463)
Salt Lake City, UT4,280 ft4,72415.0%3,000 W (3,199)5,000 W (5,552)
Denver, CO5,228 ft5,26218.3%3,000 W (3,329)5,500 W (5,777)
Albuquerque, NM5,310 ft3,99618.6%3,000 W (3,341)5,500 W (5,797)
Cheyenne, WY6,119 ft7,02821.4%3,000 W (3,461)5,500 W (6,006)
Colorado Springs, CO6,181 ft5,88821.6%3,000 W (3,471)5,500 W (6,023)
Flagstaff, AZ7,347 ft6,52625.7%3,000 W (3,662)6,500 W (6,354)

A 3,000-watt generator covers the furnace, fridge, lights and TV in every city; only the starting rating climbs, from 2,720 watts at sea level to 3,329 in Denver. Add a sump pump and a microwave, as in our calculator’s default list, and Denver needs a 5,500-watt generator and Flagstaff a 6,500.

Dot chart of generator starting watts needed for a gas furnace load, from 2,721 W in Boston to 3,662 W in Flagstaff
Eaves & Acres analysis: the same furnace load needs a higher starting rating as the elevation climbs.

Heat doesn’t trim a generator in winter: Generac’s temperature derate starts above 77°F for its liquid-cooled standby models5 and above 60°F for its air-cooled ones,18 and the warmest January average high among the Table 2 cities is 48.5°F (Denver). It matters in summer, as the Denver example below shows. The calculator applies both rules to your ZIP code.

Electric furnaces and heat pumps are a different class of load

An electric furnace makes its heat with resistance elements. Goodman’s AMST air handler takes heat kits from 3 to 25 kW; its “10 kW” kit is rated 9.6 kW and draws 40 amps at 240 volts.12 Resistance heat has no starting surge (Champion lists none for an electric water heater or space heater),1 but it carries the whole house’s heat.

A heat pump’s compressor is the same machine that cools in summer. Goodman’s 3-ton GSZ14 heat pump is rated 36,000 Btu/h for both cooling and heating. Its compressor’s rated load is 15.4 amps at 208–230 volts, about 3,540 watts at 230 volts, close to Champion’s 3,000–3,500 running watts for a 3-ton central AC. As it starts, it draws 83.9 amps (locked-rotor current), more than five times that.13,1 In deep cold, backup electric strips can add their kilowatts on top; our guide to heat pumps in cold weather explains when they come on.

Table 3. Electric heat and heat pumps: generator size at sea level
System (plus an
800 W blower)
Running
watts
Starting
watts
Portable
size
Standby
size
Heat pump, 3-ton4,3006,8005,000 W (starting rating 6,800+)10 kW
Heat pump +
4.8 kW strips
9,10011,60010,000 W10 kW
Heat pump +
9.6 kW strips
13,90016,40015,000 W17 kW
Electric furnace,
4.8 kW
5,6006,4006,500 W10 kW
Electric furnace,
9.6 kW
10,40011,20012,000 W12 kW
Electric furnace,
14.4 kW
15,20016,00017,500 W17 kW
Electric furnace,
19.2 kW
20,00020,800Above our largest portable size22 kW
Electric furnace,
24 kW
24,80025,600Above our largest portable size30 kW

Sizes come from the calculator’s standard list, with its 5% margin; check each unit’s starting rating too. Air-cooled standby units are often rated lower on natural gas: Generac’s 10 kW model gives 10,000 watts on propane but 9,000 on natural gas,19 so on natural gas the heat pump with 4.8 kW strips (9,555 watts with the margin) needs the next size up. Both systems run on 208/240 volts,12,13 so the generator must supply 240 volts at those wattages.

Worked example

Heat pump home in Denver, standby generator

Scenario
Winter: 3-ton heat pump (3,500 running, 6,000 starting), blower (800), 9.6 kW backup strips, fridge, lights and a TV with router, all at once. Summer: the same unit cooling, without strips. Station elevation 5,228 ft; January average high 48.5°F, July 91.4°F (NOAA).
Math
Winter: 15,020 running and 17,520 starting watts. Generac factor: 1 − 0.03 × 4.628 = 0.861 (no heat derate). Size: 15,020 × 1.05 ÷ 0.861 = 18,314 W; starting 20,345 W. Summer: 5,420 running and 7,920 starting watts. Factor: 0.861 × (1 − 0.017 × 1.44) = 0.840. Size: 6,774 W; starting 9,428 W.
Answer
A 20 kW standby unit for winter, whose spec sheet covers 20,345 starting watts. Summer alone would need only 10 kW: for a heat pump home, winter sets the size.

Check the rating for your fuel. Generac rates its air-cooled 20 kW model at 18,000 watts on natural gas, below the 18,314 this load needs; its 24 kW gives 21,000.18 Its air-cooled sheets also list a steeper altitude loss, about 3.5% per 1,000 feet from sea level, which raises the winter need to 19,303 running and 21,444 starting watts: still a 20 kW unit on propane, a 24 kW on natural gas.18

Photo of a white heat pump outdoor unit on a dark pad beside a gray house wall between green shrubs
A heat pump’s outdoor unit holds the compressor, the load that pushes a home into standby sizes. Photo: Tony Webster, CC BY 4.0, via Wikimedia Commons; brand logo removed by Eaves & Acres.

For backup power, a gas furnace is the far smaller load; our heat pump vs furnace comparison covers what each costs to run by city.

Inverter or conventional generator for furnace electronics

Furnaces run on control boards, and Lennox sets generator limits in its SL280DFNV gas furnace instructions: 120 volts (102 to 132), 60 Hz within 5% (57 to 63 Hz), correct polarity and a proper ground, both checked before the furnace runs on temporary power.7 They add:

Generator should have a wave form distortion of less than 5% THD

THD (total harmonic distortion) measures how far power departs from a clean wave. Generac says standard portable generators typically run 9% to 15% THD, some up to 30%, while several of its non-inverter lines (XD, XG, XC, XT-EFI and GP-EFI) stay under 6%.6

Generac inverter generators produce ≤3% THD, making them ideal for use with sensitive electronics.

So on paper an inverter generator meets Lennox’s limit and a typical conventional portable doesn’t. “Under 6%” doesn’t prove “under 5%”, so compare the spec sheet’s THD figure with your furnace manual. Not every manual sets one: the Goodman and Carrier sheets we read say nothing about generators.8,9

Photo of a portable inverter generator’s front panel with its label, outlets and switches, engine below
An inverter generator: Generac rates its own at 3% THD or less. Photo: P1898, CC BY 4.0, via Wikimedia Commons (cropped).

Polarity and ground matter too. Goodman’s wiring diagram has the control board flash rapidly for reversed polarity and tells the technician to verify the ground.9 If a furnace won’t light on generator power, that is a job for the electrician who made the connection, not for an adapter.

Getting generator power to the furnace

The Goodman and Carrier spec sheets show a furnace wired to a 115-volt supply with its own fuse or breaker,8,9 so it doesn’t plug into a generator. Honda’s manual says connections to a building’s electrical system must be made by a qualified electrician, through a transfer switch that isolates generator power from utility power. Improper connections can backfeed the utility lines and electrocute line workers.4

Carbon monoxide: where the generator goes

Carbon monoxide. The U.S. Consumer Product Safety Commission links more than 100 deaths a year in the US to portable generators. Never use one inside a home or garage, even with doors and windows open. Run it outside only, at least 20 feet from the house, with the exhaust facing away. Put battery-operated CO alarms, or alarms with battery backup, on every level of the home and outside sleeping areas.16
Diagram of a portable generator 20 feet from a house with exhaust pointed away and CO alarms on every level
CPSC’s placement rules: outside only, 20 feet or more from the house, exhaust facing away.

Our portable generator safety guide covers placement, alarms, cords and refueling, with CPSC’s records of generator deaths.

Photo of an outdoor faucet on a brick wall with the water below its spout frozen into a column of iceRelated guideAt What Temperature Do Pipes Freeze? The 20°F Threshold and Where It Hits

Next step

Note your furnace’s volts, amps and blower size, list what else must run, and enter it with your ZIP code in the generator size calculator. Its rules are on our methodology page; the generators section has our other backup-power guides.

Frequently asked questions

You can run it, but not by plugging it in yourself. Furnaces are wired to their own 115–120-volt circuit, and Honda warns that improper connections to a building’s wiring can backfeed utility lines and electrocute line workers. A licensed electrician installs the transfer switch.

Was this page helpful?

Sources

  1. 1.
    Generator Wattage Chart: Common Appliances & Tools. Champion Power Equipment, 2026. Used for: furnace fan (1/2 HP) 300–800 running and 800–1,600 starting watts; 3-ton central AC; no surge for resistance heaters Back to text
  2. 2.
    What Wattage Generator Do I Need? (wattage estimation guide). American Honda Motor Co., n.d. Used for: furnace fan, gas or fuel oil, 1/8–1/2 hp: running and starting watts Back to text
  3. 3.
    What Size Generator Do I Need? (power management). American Honda Motor Co., n.d. Used for: furnace (1/4 hp fan) 600/1,600 W example; staggering loads; quote Back to text
  4. 4.
    Owner’s Manual, Generator EG5000X. Honda Motor Co., 2009. Used for: altitude derate (about 3.5% per 1,000 ft); connections to a building by a qualified electrician through a transfer switch; backfeed warning Back to text
  5. 5.
    Spec Sheet, RG Protector Series 22–38 kW Standby Generators. Generac Power Systems, 2025. Used for: standby derates: 3% per 1,000 ft above 600 ft; 1.7% per 10°F above 77°F Back to text
Behind this guide

How this guide was made

  • Written by the Home Systems Desk and reviewed by the Data & Methodology Desk.
  • Data: blower, burner, heat-kit and compressor figures transcribed from Champion’s and Honda’s wattage charts and from Beckett, Carrier, Goodman, Lennox and Thermo Pride documents. Sizes use our generator calculator’s rule (running watts plus 5%, plus the largest single surge for starting) with Honda’s portable derate (about 3.5% per 1,000 ft) and Generac’s liquid-cooled standby derate (3% per 1,000 ft above 600 ft; 1.7% per 10°F above 77°F), with its air-cooled rule (about 3.5% per 1,000 ft; 1% per 10°F above 60°F) shown for the Denver standby example. Station elevations, heating degree days and monthly normals come from NOAA NCEI U.S. Climate Normals 1991–2020 (station nearest each ZIP code; 40,789 ZIP codes have both an elevation and a degree-day normal). Real blowers often draw less than the charts; no document we read gives a blower’s starting watts. See our methodology.
  • AI use: AI tools help us research, draft and check this guide. Every figure is checked against the source cited for it, and calculated figures come from our own code, described on the methodology page.
  • Spotted an error? Tell us and the form opens with this page’s address filled in.

Change log

  • Nov 23, 2026FAQ reorganized around current search questions: propane and oil furnaces, a furnace with a refrigerator, and 3,500- or 4,000-watt generators each get a direct answer from the page’s own worked examples; the two questions on connecting a furnace were merged. Re-checked the Champion and Honda wattage charts, Honda’s power-management example, the Lennox THD requirement, Generac’s THD article and CPSC’s carbon monoxide guidance against the live sources.
  • Oct 21, 2026The Denver heat pump example recommended a 20 kW standby unit without noting the fuel: Generac rates its air-cooled 20 kW model at 18,000 W on natural gas, below that load’s 18,314 W, so on natural gas it takes the 24 kW model. The example now says so and also gives the result under Generac’s steeper air-cooled altitude rule.
  • Oct 21, 2026The heat pump table notes the 10 kW model’s 9,000 W natural gas rating. New FAQ on a 4,000 W generator; the electric furnace FAQ now covers 5,000 W. The “20/20 rule” question moved to our portable generator safety guide. Table 2 trimmed for phones (January lows removed); the FAQ on what a 5,000 W generator runs was removed because Table 2 and our generator size calculator cover it. Re-checked the Champion, Honda, Lennox and Generac figures.
HS
Home Systems Desk

Covers heating, cooling, generators and water heaters. We maintain the generator sizing calculator and write the guides that explain what a number means before you call a contractor.

About this desk
Most read in Home Energy

Keep reading

Satellite photo of snow covering the Midwest and Northeast from the Great Lakes to the Atlantic coast in January
Home Energy Explainer

Heating Degree Days by ZIP Code and State: How They Work

A heating degree day is one degree a day averages below 65°F. How the count works, why it undercounts when you average temperatures, and NOAA 1991–2020 totals for every state, 20 cities and 40,700 ZIP codes.

13 min · Updated Nov 23
More from Home Energy
Newsletter

Seasonal reminders for your ZIP

Get a short email when it’s time to overseed, start seeds, open the pool or service your furnace, timed to your climate.

Remind me about
One or two emails a month: reminders for your ZIP and the occasional product pick or deal (some links earn us a commission). Unsubscribe anytime. Privacy.